Revised Ordinances of Honolulu
(Link to original Word Processing Version)
Article 8. Building Envelope
Sections:
32-8.1 Scope.
32-8.2 General.
32-8.3 Calculation procedures and basic requirements.
32-8.4 Prescriptive criteria.
32-8.5 Systems performance criteria.
(32-8.6 Notice to owner of cost of insulation or radiant barrier. Repealed by Ord.
01-46.)
32-8.6 Reserved.
Sec. 32-8.1 Scope.
(a) The requirements of this article apply to all buildings or portions of buildings
which provide shelter or facilities for human occupancy. The requirements apply to new
buildings and to additions which increase the floor space of existing buildings.
(b) Exception. Buildings or portions of buildings with open walls or other permanently open
elements of the building envelope.
(Added by Ord. 94-75)
Sec. 32-8.2 General.
(a) Compliance. The building envelope is in compliance with the requirements of this article
when all of the following conditions are met:
(1) The required calculation procedures of Section 32-8.3 are used, and the basic requirements
(air leakage and comfort ventilation) of Section 32-8.3 are satisfied;
(2) Opaque roof surfaces are in compliance with the prescriptive criteria, Section 32-8.4;
(3) Opaque wall surfaces are in compliance with the prescriptive criteria, Section 32-8.4 or,
alternatively, the entire wall (including glazing) is in compliance with the system performance
criteria, Section 32-8.5;
(4) Vertical glazing is in compliance with the prescriptive criteria, Section 32-8.4, or alternatively,
the entire wall (including opaque) is in compliance with the system performance criteria,
Section 32-8.5; and
(5) Horizontal glazing is in compliance with the prescriptive criteria, Section 32-8.4.
(b) Climate. If local building site climate data is not available, climate data from
a nearby location with a similar climate may be used.
(Added by Ord. 94-75)
Sec. 32-8.3 Calculation procedures and basic requirements.
(a) Overall Thermal Transmittance (Uo). The overall thermal transmittance of the opaque portion of
walls and roofs shall be calculated in accordance with Equation 8-1.
Equation 8-1
Σ UiAi U1A1 + U2A2 +...+ UnAn
Uo = ______ = _________________________
Ao Ao
where:
Uo = The area-weighted average thermal transmittance of the opaque wall or roof [Btu/h-ft2-ºF].
Ao = The gross area of the opaque elements of the wall or roof
[ft2]. (See subsection (c).)
Ui = The thermal transmittance of each individual element of the envelope assembly with
a unique U-value [Btu/h-ft2-ºF] (see subsection (b)). Equal to 1/Ri (where Ri is
the total resistance to heat flow of an individual path through an envelope
assembly).
Ai = The area of the element of the envelope assembly which has U-value,
Ui [ft2].
(b) Thermal Transmittance (Ui). The thermal transmittance of each individual element of the envelope
assembly shall be determined with due consideration of surface conductances and all major
series and parallel heat flow paths.
(c) Gross Area of Opaque Envelope Components.
(1) The gross area of an opaque roof surface consists of the total surface
of the roof assembly exposed to outside air or unconditioned spaces. The opaque
roof assembly shall exclude skylight surfaces, service openings, and overhangs.
(2) The gross area of opaque exterior wall surfaces is measured on the exterior
and includes between-floor spandrels, peripheral edges of flooring and door areas. The opaque
wall surface excludes vents, grilles, pipes and windows.
(d) Relative Solar Heat Gain (RSHG).
(1) The vertical fenestration solar heat gain limits are expressed in terms of maximum
relative solar heat gain (RSHG). Relative solar heat gain shall be calculated as
determined in this section. When a fenestration system includes an overhang or sidefins,
then the RSHG shall be calculated with either Equation 8-2 for an overhang
or Equation 8-3 for sidefins. For a single window, either the overhang multiplier,
OHM, or the sidefin multiplier, SFM, but not both, may be used for
shading credit.
or
Equation 8-2
RSHGi = SCglz,i x
OLE Object Here
x SCext,i x OHMi
Equation 8-3
RSHGi = SCglz,i x
OLE Object Here
x SCext,i x SFMi
where:
RSHGi = Relative solar heat gain.
SCglz,i = Shading coefficient of the glass alone taken from the manufacturer's literature.
ISprop = Interior and/or integral shade shading coefficient adjustment, based on the proposed type
of shade and the type of glass. Equal to the ratio of the
shading coefficient with shades to the shading coefficient of the glazing alone (SCglz).
As a default, ISprop. may be assumed to equal ISdef. (then ISprop./ISdef. =
1.0). (Unitless.)
ISdef=Default shading coefficient adjustment. For a medium-colored venetian blind with the proposed glazing.
Equal to the ratio of the shading coefficient of the fenestration with a
medium- colored venetian blind to the shading coefficient of the glazing alone. (Unitless.)
SCext = Shading coefficient of exterior shade screens or louvers. Default is 1.0. (Unitless.)
OHMi = Overhang Multiplier. Calculated as a function of Overhang Projection Factor, OPF. From
Equation 8-4 or Table 8-3.
SFMi = Sidefin Multiplier. Calculated as a function of the Sidefin Projection Factor,
SPF. From Equation 8-5 or Table 8-4.
The overhang and sidefin multipliers are calculated with the following equations.
Equation 8-4
OHMi = 1 + ai x OPFi + bi x OPFi2
where:
OHM = Overhang Multiplier.
OPF = Overhang Projection Factor. The maximum value allowed for credit is 1.5. From
Equation 8-6.
a, b = Coefficients which depend on orientation. From Table 8-1.
Equation 8-5
SFMi = 1 + ci x SPFi + di x SPFi2
where:
SFM = Sidefin Multiplier.
SPF = Sidefin Projection Factor. The maximum value allowed for credit is 1.5. From
Equation 8-7.
c, d = Coefficients which depend on orientation. From Table 8-2.
Table 8-1 -- Overhang Multiplier Coefficients
Orientation a b
North -0.440 0.123
East, West and South -0.840 0.245
Table 8-2 -- Sidefin Multiplier Coefficients
Orientation c d
North -0.81 0.27
East -0.51 0.13
South -0.65 0.16
West -0.61 0.16
The overhang and sidefin projection factors are calculated using the following equations.
where:
OPF = Overhang Projection Factor.
A = Horizontal projection of overhang.
B = Height of overhang. The vertical distance between the bottom of the overhang
and the bottom of the window.
Note: Overhangs shall extend the full width of the window to receive credit
for shading.
where:
SPF = Sidefin Projection Factor.
A = Sidefin depth, measured perpendicular to the window surface. If the left and
right sidefins have different depths, then A is the average of the two
depths.
B = Distance between sidefins. If the window width is less than the sidefin
spacing, then the average of the distance between the left sidefin and the
right edge of the window and the distance between the right sidefin and
the left edge of the window may be used. The average provides a
larger SPF and, therefore, a larger sidefin credit.
Note: Sidefins shall extend the full height of the window to receive credit
for shading.
A single sidefin shall receive shading credit if, for window orientations between true
north and either true east or west, the sidefin is on the south
side of the window. Similarly, for windows facing between true south and east
or west, a single sidefin is eligible for credit if it is on
the north side of the window.
Table 8-3 -- Overhang Multiplier, OHM
East, West
Overhang Projection Factor North and South
0.0 - 0.1 1.00 1.00
0.1 - 0.2 0.96 0.92
0.2 - 0.3 0.92 0.84
0.3 - 0.4 0.88 0.77
0.4 - 0.5 0.84 0.70
0.5 - 0.6 0.81 0.64
0.6 - 0.7 0.78 0.58
0.7 - 0.8 0.75 0.53
0.8 - 0.9 0.73 0.48
0.9 - 1.0 0.70 0.44
1.0 - 1.1 0.68 0.40
1.1 - 1.2 0.66 0.37
1.2 - 1.3 0.65 0.34
1.3 - 1.4 0.64 0.32
1.4 - 1.5 0.62 0.30
Note: Equation 8-4 for OHM may be used to provide slightly greater credit
for overhangs than the values in this table.
Table 8-4 -- Sidefin Multiplier, SFM
Sidefin Sidefin Multiplier
Projection
Factor North South East West
0.0 - 0.1 1.00 1.00 1.00 1.00
0.1 - 0.2 0.92 0.95 0.94 0.94
0.2 - 0.3 0.85 0.90 0.88 0.88
0.3 - 0.4 0.78 0.86 0.82 0.83
0.4 - 0.5 0.72 0.82 0.76 0.78
0.5 - 0.6 0.66 0.78 0.71 0.74
0.6 - 0.7 0.61 0.74 0.67 0.69
0.7 - 0.8 0.56 0.71 0.62 0.65
0.8 - 0.9 0.52 0.68 0.58 0.62
0.9 - 1.0 0.49 0.65 0.54 0.58
1.0 - 1.1 0.46 0.62 0.51 0.55
1.1 - 1.2 0.43 0.60 0.48 0.53
1.2 - 1.3 0.41 0.57 0.45 0.50
1.3 - 1.4 0.40 0.56 0.43 0.48
1.4 - 1.5 0.39 0.54 0.40 0.47
Note: Equation 8-5 for SFM may be used to provide slightly greater credit
for sidefins than the values in this table.
(2) Exterior Shading Devices. Exterior louvers or exterior sunscreens shall be allowed for compliance
in the RSHG calculations in subsection (d). In Equation 8-2 or Equation 8-3
an exterior shading device shall be described either by its shading coefficient (SCext)
or by its overhang multiplier (OHM) or sidefin multiplier (SFM). Automatic or manually
operable louvers shall be assumed to have an Overhang Projection Factor (for horizontal
louvers) or Sidefin Projection Factor (for vertical louvers) of 1.0. Projection factors for
fixed louvers and sunscreens shall be calculated as the ratio of louver width
to louver spacing (see Equations 8-6 and 8-7).
(3) Interior Shading Devices. Interior shading devices shall be allowed for compliance with the
RSHG requirements in accordance with Equations 8-2 or 8-3.
(e) Air Leakage and Comfort Ventilation. All residential buildings including hotel and motel guest
rooms shall meet the requirements of subdivision (1) for comfort ventilation. In addition,
conditioned spaces in residential buildings and hotel and motel guest rooms shall meet
the requirements of subdivision (1) and the air leakage requirements of subdivision (2).
Conditioned spaces in commercial buildings shall comply with subdivision (2). Unconditioned spaces in
commercial buildings shall comply with either subdivision (1) or subdivision (2).
(1) Comfort Ventilation.
(A) When compliance with this section is required under subsection (e), then habitable spaces
and working spaces shall meet the following requirements. Kitchens are exempt from this
section.
(i) Louvers or door catches which allow doors to be held open shall be
provided for interior doors. This requirement does not apply to hotel and motel
guest room entry doors;
(ii) A minimum of two operable openings to outside shall be provided on opposite
or adjacent walls. Operable openings include operable windows, sliding glass doors, louvers and
entry screen doors (if entry door is provided with door catches). For spaces
with only one external wall, two windows on either side of a wing
wall may be used; and
(iii) The minimum total free area for ventilation in each space shall be equal
to 12 percent of floor area. No more than 70 percent of the
total free area may be placed on one wall. For spaces employing a
wing wall, no more than 70 percent of the total free area may
be placed on one side of the wing wall.
(B) Exceptions.
(i) Spaces with wiring provided for ceiling fans. In each space, a minimum of
one ceiling fan outlet shall be provided for each 400 ft2 of floor
area. When more than one outlet is required within a space, the outlets
shall be uniformly distributed throughout the room. Wiring shall enable wall-mounted fan controls;
(ii) Hotel/motel guest rooms that are air- conditioned;
(iii) Spaces employing innovative natural ventilation designs which do not comply with this section,
but which can be shown through analysis or demonstration to provide adequate air
movement or temperature and humidity conditions for human comfort.
(2) Air Leakage. Conditioned spaces shall meet the following criteria for minimizing air leakage.
(A) The conditioned space shall be enclosed. Conditioning of unenclosed spaces is allowed only
under the provisions of Section 32-9.3(j);
(B) Fenestration and doors enclosing conditioned space shall be weatherstripped or otherwise tightly sealed
to minimize air leakage. Operable windows shall be capable of being tightly closed.
Openings which may be closed but not tightly sealed, such as jalousie windows
or louvers, may account for up to 2 percent of the wall area
enclosing the space;
(C) Commercial entrances enclosing conditioned space shall be revolving or self-closing doors to minimize
air leakage; and
(D) Exterior joints, cracks and holes in building envelope components enclosing conditioned space shall
be caulked, gasketed, weatherstripped or otherwise sealed to prevent air leakage.
(f) Roof Heat Gain Factor (RHGF). The solar heat gain limits for opaque roof
constructions are expressed in terms of the roof heat gain factor (RHGF) which
is described in Equation 8-8. The maximum allowed limits are listed in Section
32-8.4(a).
Equation 8-8
RHGF= Ur x α x RB
where:
RHGF = Roof Heat Gain Factor. [Btu/ft2-h-ºF].
Ur = overall thermal transmittance value for the gross area of opaque roof surfaces,
as defined in subsection (c). [Btu/ft2-h-ºF].
α = roof surface absorptivity. Between 0.3 and 1.0 [unitless].
RB = Radiant Barrier credit. Equals 0.33 if a radiant barrier is installed and
1.00 otherwise [unitless]. Radiant barrier installation shall comply with subsection (g) to qualify
for credit.
(g) Radiant Barrier Eligibility. To qualify for the radiant barrier credit (RB) described in
subsection (f), the installation of the radiant barrier shall meet the following criteria:
(1) The emissivity of the radiant barrier shall be less than or equal to
0.10. The manufacturer shall provide test data or documentation of the emissivity using
ASTM E-408, Test Method for Total Normal Emittances of Surfaces Using Inspection Meter
Techniques, ASTM Philadelphia, PA 19103.
(2) The radiant barrier shall be securely installed in a permanent manner using one
of the following five installation methods.
(A) Draped with the shiny side facing down over the top cord of the
truss before the roof deck is installed. A minimum air gap of 3/4
inch shall be provided between the radiant barrier and the roof deck above
at the center of the span. A minimum 3/4-inch air gap shall also
be provided between the radiant barrier and the ceiling or insulation below.
(B) Stretched with the shiny side facing down between the top cords of the
truss and stapled or otherwise secured at each side. A minimum air space
of 3/4 inch above and below is required.
(C) Stapled or otherwise secured to the bottom surface of the top cord of
the truss and draped below with the shiny side facing down. For attic
installations only. A minimum air space of 3/4 inch above and below is
required.
(D) Laid on top of the roof deck with the shiny side facing up
and a minimum 3/4-inch air gap between the radiant barrier and the roofing
material above. For open beam ceiling construction only. The roof slope shall be
greater than or equal to 14 degrees from horizontal.
(E) Laminated to the underside of the roof sheathing with at least 3/4-inch air
space below.
(3) At least one square foot of free area for ventilation shall be provided
per 150 square feet of attic floor area, or in the case of
vaulted or open beam ceilings, per 150 square feet of ceiling area. In
vaulted or open beam ceilings, the air space shall be vented with vent
area approximately evenly distributed between the top and the bottom. In vaulted ceilings,
vents shall be provided for each air space between rafters.
(Added by Ord. 94-75; Am. Ord. 01-47)
Sec. 32-8.4 Prescriptive criteria.
(a) Opaque Roof Surfaces.
(1) The roof heat gain factor (RHGF) for opaque roofs shall be less than
0.05 when calculated as described in Section 32-8.3(f).
(2) Exception. Roofs which are completely shaded from direct sunlight or attics with one
square foot of free area for ventilation per ten square feet of attic
floor area shall be exempt from the requirement in subsection (a).
(b) Opaque Wall Surfaces.
(1) The overall thermal transmittance value (Uo) for the gross area of opaque wall
surfaces, as defined in Section 32-8.3, shall be less than or equal to
0.15 for metal framed walls and 0.10 for all others. Alternatively, the R-value
of insulation shall be greater than or equal to R-11.
(2) Exceptions.
(A) Walls with a heat capacity greater than 7.5 Btu/ºF-ft2 of wall surface area;
(B) Portions of opaque walls completely shaded from direct sunlight by an overhang, adjacent
building or feature of the landscape such as a hill or cliff. The
wall must be shaded all day, throughout the year;
(C) Walls shaded by overhangs with a projection factor greater than or equal to
0.2 on north facing walls or 0.3 on all other orientations. The projection
factor equals the ratio of the horizontal projection of the overhang to the
height of the wall (measured as the vertical distance from the bottom of
the wall to the bottom outer edge of the overhang);
(D) Walls enclosing spaces which are not air-conditioned.
(c) Vertical Glazing.
(1) The relative solar heat gain (RSHG) of vertical fenestration, as defined in Section
32-8.3(d), shall be less than or equal to the appropriate value in Table
8-6. The maximum RSHG for north orientations shall be based on the window-to-wall
ratio (WWR) for north-facing walls. The maximum RSHG for all other orientations shall
be based on the combined WWR for east, west and south walls. Linear
interpolation may be used to determine the maximum allowed RSHG for WWR's which
lie within one of the ranges.
(2) Exceptions.
(A) A window area of up to 2 percent of gross exterior wall area
may exceed the RSHG limits for any given orientation;
(B) Individual windows may exceed the maximum RSHG limit as long as the area-weighted
average RSHG's for both the north orientation and the combined east, west and
south orientations are less than or equal to the maximum limit.
(C) Individual windows completely shaded from the sun are exempt from the RSHG limits
and shall be excluded from the window area calculation.
Table 8-6 -- Maximum Relative Solar Heat Gain (RSHG)
for High-Rise Residential and Nonresidential Buildings
East, West
North and South
WWR Range Max. RSHG Max. RSHG
0 - 0.15 0.85 0.65
0.15 - 0.30 0.85 0.45
0.30 - 0.45 0.65 0.30
0.45 - 0.60 0.50 0.25
0.60 - 0.75 0.40 0.20
0.75 - 1.00 0.40 0.20
(d) Horizontal Glazing (Skylights). The horizontal projection of skylight area shall be limited to
a maximum fraction of the horizontal projection of roof area which is specified
by the following equation:
Equation 8-9
A = 0.025 / SC
where:
A = Maximum allowed skylight area measured as the skylight's horizontal projection. Expressed as
a fraction of the horizontal projection of roof area. Shall be less than
or equal to 0.15.
SC = Shading coefficient of skylight; may be from manufacturer's literature.
(Added by Ord. 94-75; Am. Ord. 01-47)
Sec. 32-8.5 Systems performance criteria.
(a) Purpose. This section provides a systems approach to compliance with the wall and
window requirements of this code. This section may be used instead of Sections
32-8.3(b) and 32-8.3(c).
(b) Compliance.
(1) Walls of the building envelope are in compliance with this subsection when the
annual cooling energy flux (ACEF) attributable to transmission and solar gain for the
proposed design is less than the ACEF of the reference design. The ACEF
shall be calculated using the methods of subsection (c).
(2) The reference building and proposed design are defined as follows:
Surface Areas and Orientation. Walls of the reference building shall have the same
gross surface areas and orientations as walls in the proposed design. Glazing area
and orientation of the reference building shall be identical to the proposed design.
Shading Coefficients (SCx). The shading coefficient of glazing in the reference building shall
be equal to the relative solar heat gain requirements of Section 32-8.4(c) for
each window orientation.
Projection Factor (PF). The projection factor of the reference building shall be zero
(no overhangs) for all window orientations.
Visible Transmittance (VT). The visible transmittance of glazing in the reference building shall
be equal to the RSHG requirement of Section 32-8.4(c) for each orientation minus
0.25. The visible transmittance shall not be less than zero.
Glazing Thermal Transmittance (Uof). The glazing thermal transmittance in the reference building shall
be equal to 1.21 Btu/h-ft2-ºF.
Opaque Wall Thermal Transmittance (Wall Uo). The thermal transmittance of opaque wall surfaces
in the reference building shall be equal to the requirement specified in Section
32-8.4(b) for all orientations.
Wall Heat Capacity (HC). Wall heat capacity in the reference design shall be
equal to 1.0.
Equipment Power Density (EQUIP). The equipment power density in W/ft2 of the reference
building shall be equal to that in the proposed design. The equipment power
density in the proposed design is the average receptacle power density in W/ft2,
considering diversity, in the activity areas within 15 feet of each exterior wall.
If the equipment power density is not known for the proposed design, use
a value from Table 13-2 for both the reference building and the proposed
design. If the building occupancy is not known, use 0.5 W/ft2 for both
the reference design and the proposed design.
Lighting Power Density (LIGHTS). The lighting power density in W/ft2 of the reference
building shall be equal to that in the proposed design. The lighting power
density in the proposed design is the average for activity areas within 15
feet of each exterior wall.
If the lighting power density is not known for the proposed design, select
a value from Table 6-5 for both the reference building and the proposed
design. If the building occupancy is not known, use 1.5 W/ft2 for both
the reference building and the proposed design.
Daylighting Control Factor (DLCF). The daylighting control factor (DLCF) for the reference design
shall be determined from Equation 8-10 for each orientation. The DLCF for the
reference design shall not be greater than 1.0.
Equation 8-10
DLCFref = WWRprop x 1.67
where:
DLCFref = The daylighting control factor (DLCF) for the reference building.
WWRprop = The window wall ratio of the proposed design for each orientation.
The daylighting control factor (DLCF) for the proposed design shall be equal to
the ratio of daylighted perimeter to total perimeter and shall be calculated separately
for each orientation. The daylighted perimeter includes the width of windows and as
much as three feet of wall to the left and right of windows.
This may be determined from Equation 8-11. The DLCF for the proposed design
shall not be greater than 1.0.
Equation 8-11
DLCFprop = Σ (Pw + Pwr + Pwl) / Pt
where:
DLCFprop = Daylighting control factor for the proposed design for each orientation.
Pw = Width of each window on each orientation.
Pwr = Daylighted area to the right of each window on each orientation. This
shall be the lesser of three feet, half the distance to the next
window or the distance to a wall in the room or space that
is perpendicular to the building perimeter.
Pwl = Daylighted area to the left of each window on each orientation. Similar
to Pwr.
Pt = The total perimeter on each orientation.
Loads from Occupants. Sensible load from occupants in the reference building shall be
equal to that of the proposed design. The default is 0.6 W/ft2.
(c) Equation for Annual Cooling Energy Flux (ACEF). This section contains the external wall
equation for use in determining external wall cumulative annual cooling energy flux and
for determining compliance with the systems performance method of this section.
Seven individual terms are identified that correlate variables with physical meaning such as
U-values, internal gains, and weather-related variables.
CLU,
CLUO,
CLXUO: Terms that correlate the cumulative annual cooling loads with the thermal transmittance of
the wall.
CLM: Term that correlates the cumulative annual cooling loads with the heat capacity of
the wall.
CLG: Term that correlates the cumulative annual cooling loads with the internal gains from
occupant light and equipment.
CLS: Term that correlates the cumulative annual cooling loads with the incident solar gains.
CLC: Term that correlates the cumulative annual cooling loads with the climate variables for
a specific location.
(1) Cooling Equation.
Equation 8-12
WCc or Cl = Σ [CLUOi + CLXUOi
+ CLGi + CLSi + CLCi + Σ(CLUi,j + CLMi,j )]
If WC c or C 1 < 0.0, then WC c or C 1 is set equal
to 0.0.
where:
Subscripts
i = matrix consideration for each given orientation.
j = matrix consideration for each wall mass construction type for the given
orientation.
Indices
m = number of wall construction types per orientation.
n = number of wall orientations.
Variables
CLUOi = FCi x UOCi[CUO1i x EAi x VSi x CDD50 + CUO2i x
Gi + CUO3i x Gi2 x EAi2 x VSi x CDD50 + CUO4i
x Gi2 x EAi2 x VSi x CDD65]
CLXUOi = FCi(1/UOCi)[CXUO1i x EAi x VSi x CDD50 + CXUO2i x EAi(VSi x
CDD50)2 + CXUO3i x Gi x CDD50 + CXUO4i x Gi2 x EAi2
x VSi x CDD50 + CXUO5i x Gi2 x CDD65]
CLGi = FCi{Gi[CG1i + CG2i x CDD50 + CG3i x EAi(VSi x CDD50)2 +
CG4i x EAi2 x VSi x CDD50 + CG5i x CDD65 + CG6i
x CDD503 + CG7i x CDD653] + Gi2[CG8i x EAi x VSi x
CDD50 + CG9i x EAi2 x VSi x CDD50]}
CLSi = FCi{EAi[CS1i + CS2i x VSi x CDD50 + CS3i(VSi x CDD50)2 +
CS4i x VSi x CDD65 + CS5i(VSi x CDD65)2] + EAi2[CS6i + CS7i(VSi
x CDD65)2]}
CLCi = FCi[CC1i x CDD50 + CC2i x CDD502 + CC3i x CDH80 +
CC4i x CDH802 + CC5i x CDD65 + CC6i(VSi x CDD65)2 + CC7i
x VSi x CDD50 + CC8i(VSi x CDD50)2 + CC9i(VSi x CDH80)2 +
CC10i x VSi + CC11i x DR + CC12i x DR2 + CC13i]
CLUi,j = FOi,j x Uow,i[CU1i x CDH80 + CU2i x CDH802 + CU3i(VSi x
CDH80)2 + CU4i x DR]
CLMi,j = FOi,j x CMCi,j[CM1i + CM2i x EAi x VSi x CDD50
+ CM3i x EAi x VSi x CDD65 + CM4i x EAi2 x
VSi x CDD50 + CM5i x Gi2 x CDD65 + CM6i x Gi
x CDD50 + CM7i x Gi x CDD65 + CM8i x Gi x
EAi x VSi x CDD50]
Note: The coefficients for various orientations in the above equations are shown in Table
8-8.
Climate data
CDD50 = Cooling degree-days base 50ºF.
CDD65 = Cooling degree-days base 65ºF.
CDH80 = Cooling degree-hours base 80ºF.
DR = average daily temperature range for warmest month.
VSi = annual average daily incident solar energy on facade under consideration, Btu/(ft2-day).
Building Data
FCi = ratio, wall area (opaque and glazed) of zone under consideration divided by
total wall area (opaque and glazed) of all zones.
FOi,j = ratio, opaque wall area of zone under consideration divided by total wall
area (opaque and glazed) of all zones. If multiple mass constructions are present,
the FOi,j is calculated for each construction j and used to form the
area weighted mass correction.
Uow,i = area average U-value of opaque walls (including those of mass construction) in
zone under consideration, Btu/(h-ft2-ºF).
UOCi = area average U-value of wall (opaque and glazed, evaluated under cooling conditions)
in zone under consideration, Btu/(h-ft2-ºF).
WWRi = window wall ratio for zone under consideration; defined as fenestration area divided
by total wall area (opaque and glazed).
EAi = effective aperture fraction for zone under consideration, where:
Equation 8-13
EAi = WWRi x RSHGi
and
RSHGi = the relative solar heat gain for the fenestration in a given orientation,
as determined from Section 32-8.3(d).
Internal Load
Equation 8-14
Gi = Ep,i + Lp,i (1 - Rc,i x Kd,i ) + Ol,i
where:
Gi = effective internal gain (W/ft2) for zone under consideration.
Ep,i = equipment power, from subsection (b).
Lp,i = lighting power, from subsection (b).
Ol,i = occupant load adjustment, from subsection (b).
Rc,i = for a specified orientation, the ratio of the daylighting area of the
space to the total area of the space.
Equation 8-15
Kd,i = 5.871(WWRi x VLTi x OHMi ) - 13.311(WWRi x VLTi x
OHMi )2
If WWR i x VLT i x OHM i is greater than 0.22, then K d,i is
set equal to 0.647.
where:
WWRi = as defined above under Building Data.
VLTi = visible light transmittance of the glazing material, as defined in subsection (b).
OHMi = Overhang multiplier, from Section 32-8.3(d).
CMCi,j = mass correction from Eq 8-16. If multiple mass constructions are present, then
each CMCi,j is evaluated separately and combined by area weighting. If the U-value
of the mass wall is greater than 0.40, then Uow = 0.4 shall
be used to calculate the CMCi,j. If the value of HC is greater
than 20, then HC = 20 shall be used to calculate the CMCi,j.
(2) Cooling Delta Load Factor Equations. Equation 8-16 is used to predict the Cooling
Delta Load Factor values.
Equation 8-16
CMC = Cooling Delta Load Factor =
[1 - e-CP1(HC-1)]
x
OLE Object Here
x
where:
HC = Wall Heat Capacity (Btu/ft2-ºF).
U = Wall U-Value (Btu/h-ft2-ºF).
A = (Cooling degree-hours base 80ºF)/10,000 + 2 (ºF-h).
B = (Daily Range)/10 + 1(ºF).
CP1 = C5
CP2 = C15/B3 + C16/(A2B2) + C17
CP3 = C1/A3 + C2B3 + C3/(A2B) + C4
CP4 = C12/(A2B2) + C13/B3 + C14
CP5 = C18
CP6 = C6B LN(A) + C7
LN = Natural Logarithm
CP7 = C19/(A2B2) + C20/(AB) + C21A2/B + C22
CP8 = C8/(A2B2) + C9/(AB) + C10/(A2B) + C11
The coefficients C1 through C22 are taken from Table 8-7.
Table 8-7 -- Cooling Delta Load Coefficients
Insulation Position
Coefficient Exterior Integral Interior
C 1 220.724503 139.105667 181.616776
C 2 -.056589 -.033991 -.055196
C 3 -118.835388 -10.326704 -34.158966
C 4 -13.674420 -20.867386 -25.591934
C 5 .236381 .283882 .081029
C 6 .959588 .305851 1.418998
C 7 -.255004 .022622 .432421
C 8 -905.677979 -307.943848 -1882.926758
C 9 425.191895 80.209610 443.195801
C 10 -2.510600 .049955 .430200
C 11 -43.387955 -5.989545 -28.285065
C 12 -259.723389 -11.396114 -63.562256
C 13 -33.975525 .366851 20.844650
C 14 20.488235 30.253494 9.817521
C 15 -26.209152 8.833706 24.459824
C 16 -241.173386 -22.254623 -70.337494
C 17 18.897781 29.329697 9.884280
C 18 -.353790 -.023878 -.114646
C 19 156.305634 63.322754 326.344727
C 20 -74.098999 -16.334656 -77.635498
C 21 .445363 -.011114 -.074788
C 22 7.496696 1.295576 5.204088
Table 8-8
Cooling
Coefficients North East South West
CU1 0.001539 0.003315 0.003153 0.00321
CU2 -0.308548E-07 -0.896618E-07 -0.712993E-07 -0.810530E-07
CU3 0.799493E-13 0.379280E-13 0.183083E-13 0.339810E-13
CU4 -0.079647 0.163114 0.286458 0.11178
CM1 0.32314 0.515262 0.71477 0.752643
CM2 0.153060E-05 0.138197E-05 0.161630E-05 0.142228E-05
CM3 -0.204322E-05 -0.160240E-05 -0.211063E-05 -0.197938E-05
CM4 -0.753665E-06 -0.767849E-06 -0.664430E-06 -0.740067E-06
CM5 -0.100472E-05 0 0.801057E-05 0.315193E-05
CM6 0.366708E-04 0.356503E-04 0.448106E-04 0.296012E-04
CM7 -0.673045E-04 -0.640938E-04 -0.000119 -0.766719E-04
CM8 -0.238335E-07 -0.472534E-07 -0.497469E-07 0
CUO1 -0.651094E-05 -0.838669E-05 -0.888996E-05 -0.756465E-05
CUO2 -1.040207 -1.507235 -1.512625 -1.238545
CUO3 -0.438254E-05 -0.278828E-05 -0.231352E-05 -0.412567E-05
CUO4 0.126580E-04 0.809874E-05 0.736219E-05 0.106712E-04
CXUO1 0.103744E-05 0.119338E-05 0.118588E-05 0.123251E-05
CXUO2 -0.132180E-12 -0.134656E-12 -0.116252E-12 -0.130002E-12
CXUO3 0.275554E-04 0.202621E-04 0.202365E-04 0.236964E-04
CXUO4 0.974090E-07 0.117514E-06 0.939207E-07 0.136276E-06
CXUO5 -0.118247E-04 -0.909694E-05 -0.909192E-05 -0.111077E-04
CG1 0.891286 0.583388 0.393756 0.948654
CG2 0.001479 0.001931 0.002081 0.001662
CG3 -0.552042E-12 -0.282139E-12 -0.284766E-12 -0.455720E-12
CG4 0.252311E-05 0.370821E-05 0.430536E-05 0.591511E-05
CG5 -0.001151 -0.001745 -0.001864 -0.00153
CG6 0.195243E-11 0 -0.296055E-11 0.316358E-11
CG7 -0.835805E-11 0.101089E-10 0.330027E-10 0
CG8 0.141022E-05 0.753875E-06 0.713300E-06 0.970752E-06
CG9 -0.238887E-05 -0.164961E-05 -0.163927E-05 -0.197363E-05
CS1 46.9871 33.9683 18.32016 29.3089
CS2 0.348091E-04 0.374118E-04 0.340490E-04 0.502498E-04
CS3 0 0 0.271313E-11 0
CS4 -0.166409E-04 0.694779E-05 -0.282181E-04 -0.277158E-04
CS5 0.842765E-11 0 -0.304677E-11 0.291137E-11
CS6 -56.5446 0 26.9954 14.9771
CS7 -0.134764E-10 -0.588097E-11 -0.650089E-11 -0.789218E-11
CC1 0.002747 0 0.010349 0.001865
CC2 0 0.318928E-06 -0.304413E-06 0
CC3 -0.000348 0.000319 0.00024 0.000565
CC4 0.122123E-07 -0.775318E-07 -0.271443E-07 -0.544380E-07
CC5 0.012112 0.011894 0.013248 0.009236
CC6 0.104027E-11 -0.622661E-12 -0.205178E-11 0
CC7 -0.124013E-04 -0.706280E-05 -0.165377E-04 -0.602685E-05
CC8 0 0 0.820869E-12 0
CC9 -0.375797E-13 0.606235E-13 0.197598E-13 0.389425E-13
CC10 0.030056 0.023121 0.0265 0.01704
CC11 0 0 -0.271026 -0.244274
CC12 0.002138 0.001103 0.006368 0.007323
CC13 -12.8674 -13.16522 -18.271 -10.1285
(Sec. 32-8.6 Notice to owner of cost of insulation or radiant barrier. Repealed by
Ord. 01-46.)
Sec. 32-8.6 Reserved.
Article 9. Heating, Ventilating and Air Conditioning
(HVAC) Systems
Sections:
32-9.1 Scope.
32-9.2 General.
32-9.3 Basic requirements.
32-9.4 Prescriptive criteria.
Sec. 32-9.1 Scope.
(a) The requirements of this article apply to all new HVAC systems or system
components in both new and existing buildings.
(b) Exception. This article does not apply to the maintenance and repair of existing
systems.
(Added by Ord. 94-75)
Sec. 32-9.2 General.
The requirements in this article represent minimum design criteria. Where applicable, the state
department of health (DOH) Administrative Rules, Title 11, Chapter 39, enforced by the
DOH, shall apply to ventilation and air conditioning. (Added by Ord. 94-75)
Sec. 32-9.3 Basic requirements.
(a) Load Calculations.
(1) Calculation Procedures. Cooling system design loads for the purpose of sizing systems and
equipment shall be determined in accordance with the procedures described in the ASHRAE
Handbook, 1989 Fundamentals or a similar computation procedure. For those design parameters addressed
in (2) through (9), the values specified shall be used.
(2) Indoor Design Conditions. Indoor design temperature and humidity conditions for general comfort applications
shall be in accordance with the comfort criteria established in ANSI/ASHRAE Standard 55-1981
Thermal Environmental Conditions for Human Occupancy, or Chapter 8 of the ASHRAE Handbook,
1989 Fundamentals, or both, except that winter humidification and summer dehumidification are not
required.
(3) Outdoor Design Conditions. Outdoor design conditions shall be selected from "Climatic Data for
Region X Arizona, California, Hawaii, Nevada," Golden Gate and Southern California Chapters, ASHRAE,
Fifth Edition, May 1982, or from data obtained from the National Climatic Center
or a similar recognized weather data source. Cooling design temperatures shall be no
greater than the 0.5 percent annualized value.
(4) Ventilation. Outdoor air ventilation loads shall be based on ventilation rates specified in
subsection (f).
(5) Envelope. Envelope cooling loads shall be based on envelope characteristics, such as thermal
conductance, shading coefficient, and air leakage, consistent with the values used to demonstrate
compliance with Article 8.
(6) Lighting. Lighting loads shall be based on actual design lighting levels or power
budgets consistent with Article 6.
(7) Other Loads. Other HVAC system loads, such as those due to people and
equipment, shall be based on design data compiled from one or more of
the following sources:
(A) Actual information based on the intended use of the building;
(B) Published data from manufacturers' technical publications;
(C) Technical society publications such as the ASHRAE Handbooks, 1991 HVAC Applications and 1992
HVAC Systems and Equipment;
(D) Alereza, "Estimates of recommended heat gains due to commercial appliances and equipment," ASHRAE
Transactions, Vol. 90, Pt 2A, pp. 25-58, 1984.
(E) Default values to be used in determining the design energy budget in Article
13 are taken from Tables 13-1, 13-2, and 13-4;
(F) Other data based on designer's experience of loads and occupancy patterns.
(8) Safety Factor. Design loads may, at the designer's option, be increased by as
much as 10 percent to account for unexpected loads or changes in space
usage.
(9) Pickup Loads. Transient loads such as cool-down loads which occur after off-hour setback
or shutoff, may be calculated from basic principles, based on the heat capacity
of the building and its contents, the level of setback, and desired recovery
time, or may be assumed to be up to l0 percent of the
steady-state cooling design loads. The steady-state load may include a safety factor in
accordance with subdivision (8).
(b) Separate Air Distribution Systems.
(1) Zones with special process temperature requirements, humidity requirements, or both, shall be served
by separate air distribution systems from those serving zones requiring only comfort conditions,
or shall include supplementary provisions so that the primary systems may be specifically
controlled for comfort purposes only.
(2) Exception. Zones that require only comfort cooling and are served by a system
primarily used for process temperature and humidity control, need not be served by
a separate system if the total supply air to these comfort zones is
no more than 25 percent of the total system supply air, or the
total conditioned floor area of the zones is less than 1,000 ft2.
(c) Temperature Controls.
(1) System Control. Each HVAC system shall include at least one temperature control device.
(2) Zone Controls.
(A) The supply of cooling energy to each zone shall be controlled by individual
thermostatic controls responding to temperature within the zone.
(B) Exceptions.
(i) Independent perimeter systems that are designed to offset only envelope heat gains may
serve one or more zones also served by an interior system, with the
following limitations:
1. The perimeter system shall include at least one thermostatic control zone for each
building exposure having exterior walls facing only one orientation for 50 contiguous feet
or more;
2. The perimeter system cooling supply shall be controlled by thermostat located within the
zone served by the system.
(ii) A dwelling unit may be considered a single zone.
(3) Thermostats shall be shaded from direct solar radiation and shall be isolated from
heat gain due to large equipment and machinery.
(4) Where used to control comfort cooling, zone thermostatic controls shall be capable of
being set, locally or remotely, by adjustment or selection of sensors, up to
85 degrees Fahrenheit or higher.
(d) Off-hour and Interlock Controls.
(1) Off-hour Controls.
(A) HVAC systems shall be equipped with automatic controls capable of accomplishing a reduction
of energy use through control setback or equipment shutdown during periods of nonuse
or alternate use of the spaces served by the system.
(B) Exceptions.
(i) Systems serving areas expected to operate continuously;
(ii) Where it can be shown that setback or shutdown will not result in
a decrease in overall building energy costs;
(iii) Equipment with full load demands of 2 kW (6826 Btu/hr) or less may
be controlled by readily accessible manual off-hour controls;
(iv) Where process conditioning is required on a 24-hour basis.
(2) Systems that serve zones which can be expected to operate non-simultaneously for more
than 750 hours per year shall include isolation devices and controls to shut
off or set back the supply of cooling to each zone independently. Isolation
is not required for zones expected to operate continuously or expected to be
inoperative only when all other zones are inoperative.
For buildings where occupancy patterns are not known at the time of system
design, such as speculative buildings, isolation areas may be predesignated.
Zones may be grouped into a single isolation area provided that the total
conditioned floor area does not exceed 25,000 ft2 per group nor include more
than one floor.
(3) Operable doors leading from a conditioned space to a balcony or patio in
hotel or motel guest rooms shall be provided with interlock controls to disable
cooling of the space while the door is open.
(e) Dehumidification. Where a humidistat is used for comfort dehumidification, it shall be capable
of being set to prevent the use of fossil fuel or electricity to
reduce relative humidities below 60 percent.
(f) Ventilation.
(1) Outdoor air ventilation rates shall not exceed the minimum rates required by ASHRAE
Standard 62-1989 by more than 10 percent.
(2) Exception. Outdoor air quantities may be greater if required because of special occupancy
or process requirements, source control of air contamination or local codes, or if
it can be shown that the additional outside air does not increase overall
building energy costs.
(g) Materials and Construction.
(1) Insulation required by subdivisions (2) and (3) shall be suitably protected from damage.
Insulation should be installed in accordance with MICA Commercial and Industrial Insulation Standards,
1983.
(2) Piping Insulation.
(A) All HVAC system piping shall be thermally insulated in accordance with Table 9-1.
(B) Exceptions. Piping insulation shall not be required in any of the following cases:
(i) Factory installed piping within HVAC equipment tested and rated in accordance with Section
32-10.3;
(ii) Piping that conveys fluids which have a design operating temperature range between 55
degrees Fahrenheit and 105 degrees Fahrenheit;
(iii) Piping that conveys fluids which have not been heated or cooled through the
use of fossil fuels or electricity;
(iv) Where it can be shown that the heat gain and/or heat loss to
or from piping without insulation will not increase building energy costs.
Table 9-1 -- Minimum Pipe Insulation (Inches) a
Insulation
Conductivity
Fluid Nominal Pipe Diameter (in)
Design Cond. Mean
Operating Range, Rating
Temp., Btu·in/ Temp., Runouts b 1 and 1.25 2.5 5 8
Range °F h·ft 3 °F °F up to 2 less to 2 to 4
& 6 and up
Heating Systems (Steam, Steam Condensate, and Hot Water)
Above 350 0.32-0.34 250 1.5 2.5 2.5 3.0 3.5 3.5
251-350 0.29-0.31 200 1.5 2.0 2.5 2.5 3.5 3.5
201-250 0.27-0.30 150 1.0 1.5 1.5 2.0 2.0 3.5
141-200 0.25-0.29 125 0.5 1.5 1.5 1.5 1.5 1.5
105-140 0.24-0.28 100 0.5 1.0 1.0 1.0 1.5 1.5
Domestic and Service Hot Water c
105 and 0.24-0.28 100 0.5 1.0 1.0 1.5 1.5 1.5
Greater
Cooling Systems (Chilled Water, Brine & Refrigerant)d
40-55 0.23-0.27 75 0.5 0.5 0.75 1.0 1.0 1.0
Below 40 0.23-0.27 75 1.0 1.0 1.5 1.5 1.5 1.5
a. For minimum thicknesses of alternative insulation types, see Section 32-9.3(g)(2).
b. Runouts to individual terminal units not exceeding 12 feet in length.
c. Applies to recirculation sections of service or domestic hot water systems and first
8 feet from storage tank for nonrecirculating systems.
d. The required minimum thicknesses do not consider water vapor transmission and condensation. Additional
insulation and/or vapor retarders may be required to limit water vapor transmission and
condensation.
Alternative Insulation Types. Insulation thicknesses in Table 9-1 are based on insulation with
thermal conductivities within the range listed in Table 9-l for each fluid operating
temperature range, rated in accordance with ASTM C 335-84 at the mean temperature
listed in the table. For insulation that has a conductivity outside the range
shown in Table 9-l, for the applicable fluid operating temperature range at the
mean rating temperature shown, when rounded to the nearest 1/100th Btu·inch/h·°F·ft2, the minimum
thicknesses shall be determined in accordance with Equation 9-1:
Equation 9-1
T = PR [(1 + t / PR)K/k - 1]
where:
T = minimum insulation thickness for material with conductivity K, inches.
PR = pipe actual outside radius, in.
t = insulation thickness from Table 9-1, in.
K = conductivity of alternate material at the mean rating temperature indicated in Table
9-1 for the applicable fluid temperature range, Btu·in/h·°F·ft2.
k = the lower value of the conductivity range listed in Table 9-1 for
the applicable fluid temperature range, Btu·in/h·°F·ft2.
(3) Air Handling System Insulation.
(A) All air handling ducts and plenums installed as part of an HVAC air
distribution system shall be thermally insulated in accordance with Table 9-2.
(B) Exceptions.
(i) Factory installed plenums, casings, or ductwork furnished as a part of HVAC equipment
tested and rated in accordance with Section 32-10.3.
(ii) Where it can be shown that the heat gain to or heat loss
from ducts without insulation will not increase building energy costs.
Table 9-2 -- Minimum Duct Insulation a
Temperature Insulation
Differenceb R-valuec
°F ft 2 ·h·°F/Btu
Exterior of Building all 8.0
Inside of building envelope in < 15 Not Required
conditioned or unconditioned > 15 to < 40 3.3
spacese > 40 5.0d
a. Insulation R-values shown are for the insulation as installed and do not include
film resistance. The required minimum thicknesses do not consider water vapor transmission and
condensation. Additional insulation and/or vapor retarders may be required to limit vapor transmission
and condensation. Where exterior walls are used as plenum walls, wall insulation shall
be as required by the most restrictive conditions of this article or Article
8.
b. Temperature difference is at design conditions (see Section 32-9.3(a)) between the space within
which the duct is located and the design air temperature in the duct.
c. Insulation resistance measured on a horizontal plane in accordance with ASTM C518-85 at
a mean temperature of 75 degrees Fahrenheit at the installed insulation thickness.
d. Insulation resistance for runouts to terminal devices less than 10 feet in length
need not exceed 3.3 ft2·h·°F/Btu.
e. Unconditioned spaces include crawl spaces and attics.
(4) Duct Construction.
(A) All air handling ductwork and plenums shall be constructed and erected in accordance
with the following SMACNA publications:
(i) HVAC Duct Construction Standards -- Metal and Flexible, 1985;
(ii) HVAC Duct Leakage Test Manual, 1985;
(iii) TIMA Fibrous Glass Duct Construction Standards, 1989.
(B) In addition to the above-referenced standards, the following are required:
(i) Leakage Tests. Ductwork which is intended to operate at static pressures in excess
of 3 in. wc shall be leak-tested and be in conformance with sections
of the HVAC Duct Leakage Test Manual, as follows: Test procedures shall be
in accordance with those outlined in Section 5 of the manual, or equivalent;
test reports shall be provided in accordance with Section 6 of the manual,
or equivalent; the tested duct leakage class at a test pressure equal to
the design duct pressure class rating shall be equal to or less than
Leakage Class 6 as defined in Section 4.l of the manual. Leakage testing
may be limited to representative sections of the duct system, but in no
case shall such tested sections include less than 25 percent of the total
installed duct area for the designated pressure class.
(ii) Additional Sealing. Where supply ductwork and plenums that are intended to operate
at static pressures from l/4 in. to 2 in. wc inclusive, are located
outside of the conditioned space or in return plenums, joints shall be sealed
in accordance with Seal Class C, as defined in the SMACNA manuals referenced
above. Pressure- sensitive tape shall not be used as the primary sealant where
such ducts are intended to operate at static pressures of 1 in. wc
or greater.
(h) Energy Recovery. Condenser heat recovery from air conditioning or refrigeration equipment is required
for any single cooling system larger than 10 tons of cooling capacity or
compressor size of greater than 15 hp for buildings with service hot water
heaters with more than 75,000 Btu/h or 12 kW input rating, unless an
alternative system can be shown to have a lower life-cycle cost as determined
in accordance with procedures defined by the National Institute of Standards and Technology
(NIST) Life-Cycle Costing Manual for the Federal Energy Management Program, NIST Handbook 135,
and its supplement, Energy Price Indices and Discount Factors for Life-Cycle Cost Analysis.
Assumptions used in any calculation should use the latest price indices and discount
factors available at the time the calculation is submitted to the city.
(i) Completion Requirements.
(1) Operating and Maintenance Manual. An operating and maintenance manual shall be provided to
the building owner. The manual shall include basic data relating to the operation
and maintenance of HVAC systems and equipment. Required routine maintenance actions shall be
clearly identified. Where applicable, HVAC control information such as diagrams, schematics, control sequence
descriptions, and maintenance and calibration information shall be included.
(2) Air System Balancing.
(A) Air system balancing shall be accomplished in a manner to first minimize throttling
losses, then fan speed shall be adjusted to meet design flow conditions. Balancing
procedures shall be in accordance with those established by the National Environmental Balancing
Bureau (NEBB) Procedural Standards (1983), the Association of Air Balancing Council (AABC) National
Standards (1982), or equivalent procedures.
(B) Exception. Damper throttling may be used for air system balancing with fan motors
of 1 hp or less, or if throttling results in no greater than
1/3 hp fan horsepower draw above that required if the fan speed were
adjusted.
(3) Hydronic System Balancing.
(A) Hydronic system balancing shall be accomplished in a manner to first minimize throttling
losses, then the pump impeller shall be trimmed or pump speed shall be
adjusted to meet flow conditions.
(B) Exceptions. Valve throttling may be used for hydronic system balancing under any of
the following conditions:
(i) Pumps with pump motors of 10 hp or less;
(ii) If throttling results in no greater than three (3) pump horsepower draw above
that required if the impeller were trimmed;
(iii) To reserve additional pump pressure capability in open-circuit piping systems subject to fouling.
Valve throttling pressure drop shall not exceed that expected for future fouling;
(iv) Where it can be shown that throttling will not increase overall building energy
costs.
(j) Cooling of Unenclosed Spaces.
(1) Cooling systems for unenclosed spaces shall meet the following requirements:
(A) Cooling system capacity shall be no greater than 20 Btu/hr per ft2 of
floor area or 400 Btu/hr per occupant, whichever is greater. The estimated number
of occupants shall be based on the intended average occupancy and shall not
exceed the Estimated Maximum Occupancy listed in Table 2 of ASHRAE Standard 62-1989.
(B) The floor area used to calculate the allowed cooling capacity shall be limited
by a perimeter defined as follows:
(i) The perimeter shall not extend beyond the location of the ceiling air supply
diffusers or the throw of the side wall diffusers.
(ii) The perimeter shall be set back at least 10 feet from the opening
to the outside, which is defined by the outer edge of the ceiling
or overhanging roof.
(iii) The perimeter shall be bounded on at least one side by a permanent,
ceiling-height physical obstruction such as a wall or fixed window.
(k) System Commissioning.
(1) HVAC control systems shall be tested to assure that control elements are calibrated,
adjusted, and in proper working condition.
(2) For projects larger than 50,000 ft2 (4600 m2) conditioned area, detailed instructions for
commissioning HVAC systems shall be provided by the designer in plans and specifications.
(Added by Ord. 94-75; Am. Ord. 01-47)
Sec. 32-9.4 Prescriptive criteria.
(a) System and Equipment Sizing.
(1) HVAC systems and equipment shall be sized to provide no more than the
space and system loads calculated in accordance with Section 32-9.3(a).
(2) Exceptions.
(A) Equipment capacity may exceed the design load, provided the equipment selected is the
smallest size needed to meet the load within available options of the desired
equipment line.
(B) Equipment whose capacity exceeds the design load may be specified if oversizing the
equipment can be shown to not increase the overall annual energy costs.
(C) Standby equipment may be installed if controls and devices are provided which allow
standby equipment to operate automatically only when the primary equipment is not operating.
(D) Multiple units of the same equipment type, such as multiple chillers and boilers,
with combined capacities exceeding the design load may be specified to operate concurrently
only if controls are provided that sequence or otherwise optimally control the operation
of each unit based on load.
(E) For a single piece of equipment which has both heating and cooling capability,
only the cooling function need meet the requirements of this section. Capacity for
the heating function shall be, within available equipment options, the smallest size necessary
to meet the load.
(b) Zone Controls.
(1) Zone thermostatic and humidistatic controls shall prevent:
(A) Reheating;
(B) Recooling;
(C) Mixing or simultaneous supply of air that has been previously mechanically heated and
air that has been previously cooled;
(D) Other simultaneous operation of heating and cooling systems to the same zone.
(2) Exceptions.
(A) Variable air volume systems which, during periods of occupancy, are designed to reduce
the air supply to each zone to a minimum before reheating, recooling, or
mixing takes place. This minimum volume shall be no greater than the largest
of the following:
(i) 30 percent of the peak supply volume;
(ii) The minimum allowed to meet ventilation requirements of Section 32-9.3(f);
(iii) 0.4 cfm/ft2 of zone conditioned floor area;
(B) Zones where special pressurization relationships or cross-contamination requirements are such that variable air
volume systems are impractical, such as some areas of hospitals and laboratories;
(C) At least 75 percent of the energy for reheating or for providing warm
air in mixing systems is provided from a site-recovered or site-solar energy source;
(D) Zones where specified humidity levels are required to satisfy process needs, such as
computer rooms and museums. See Section 32-9.3(b);
(E) Zones with a peak supply air quantity of 300 cfm or less.
(c) Fan System Design Criteria.
(1) General.
(A) The following design criteria apply to all HVAC fan systems used for comfort
ventilating and/or air conditioning. For the purposes of this section, the energy demand
of a fan system is the sum of the demand of all fans
which are required to operate at design conditions to supply air from the
cooling source to the conditioned space(s) and return it to the source or
exhaust it to the outdoors.
(B) Exceptions.
(i) Systems with total fan system motor power of l0 hp or less;
(ii) Unitary equipment for which the energy used by the fan is considered in
the efficiency ratings of Section 32-10.3;
(iii) For the purposes of subsection (c), total fan energy demand need not include
the additional power required by air treatment or filtering systems with final pressure
drops in excess of 1.0 in. wc.
(2) Constant Volume Fan Systems. For fan systems which provide a constant air volume
whenever the fans are operating, the power required by the motors for the
combined fan system at design conditions shall not exceed 0.8 W/cfm of supply
air.
(3) Variable Air Volume (VAV) Fan Systems.
(A) For fan systems which are able to vary system air volume automatically as
a function of load, the power required by the motors for the combined
fan system shall not exceed l.25 W/cfm of supply air at design conditions.
(B) Individual VAV fans with motors 25 hp and larger shall include controls and
devices necessary for the fan motor to demand no more than 50 percent
of design wattage at 50 percent of design air volume, based on manufacturer's
test data.
(d) Pumping System Design Criteria.
(1) General.
(A) The following design criteria apply to all HVAC pumping systems used for comfort
air conditioning. For the purposes of subsection (d), the energy demand of a
pumping system is the sum of the demand of all pumps which are
required to operate at design conditions to supply fluid from the cooling source
to the conditioned space(s) or heat transfer devices(s) and return it to the
source.
(B) Exception. Systems with total pump system motor power of 10 hp or less.
(2) Friction Rate. Piping systems should be designed at a friction pressure loss rate
of no more than 4 feet of water per 100 equivalent feet of
pipe. Note: Lower friction rates may be required for proper noise or corrosion
control.
(3) Variable Flow.
(A) Pumping systems which serve control valves designed to modulate or step open and
closed as a function of load, shall be designed for variable fluid flow.
The system shall be capable of reducing system flow to 50 percent of
design flow or less. Flow may be varied with variable speed driven pumps
or staged multiple pumps.
(B) Exceptions.
(i) Dedicated equipment pumps separated from modulation control valves in a primary/secondary loop arrangement.
Secondary pumps shall comply with (A);
(ii) Systems that serve no more than one control valve;
(iii) Systems that include supply temperature reset controls in accordance with subsection (e)(2) without
exception;
(iv) Where the overall building energy costs resulting from an alternative design can be
shown to be no more than those from a variable flow system.
(e) System Temperature Reset Controls.
(1) Air Systems.
(A) Systems supplying cooled air to multiple zones shall include controls which automatically reset
supply air temperatures by representative building loads or by outside air temperature. Temperature
shall be reset by at least 25 percent of the design supply-air-to-room-air temperature
difference. Zones which are expected to experience relatively constant loads, such as interior
zones, shall be designed for the fully reset supply temperature.
(B) Exceptions.
(i) Systems which comply with subsection (b) without using exceptions (2)(A) or (2)(B);
(ii) Where it can be shown that supply air temperature reset increases overall building
annual energy costs.
(2) Hydronic Systems.
(A) Systems supplying chilled water to comfort air conditioning systems shall include controls which
automatically reset supply water temperatures by representative building loads (including return water temperature)
or by outside air temperature. Temperature shall be reset by at least 25
percent of the design supply-to-return water temperature difference.
(B) Exceptions.
(i) Systems that comply with subsection (d)(3) without exception;
(ii) Where it can be shown that supply temperature reset increases overall building annual
energy costs;
(iii) Systems for which supply temperature reset controls cannot be implemented without causing improper
operation of heating, cooling, humidification, or dehumidification systems;
(iv) Systems with less than 600,000 Btu/hr design capacity.
(f) Kitchen Hoods.
(1) Individual kitchen exhaust hoods larger than 5000 cfm (2500 L/s) shall be provided
with make-up air sized for at least 50 per cent of exhaust air
volume that is uncooled or cooled without the use of mechanical cooling.
(2) Exceptions:
(A) Where hoods are used to exhaust ventilation air which would otherwise exfiltrate or
be exhausted by other fan systems.
(B) Certified grease extractor hoods that require a face velocity no greater than 60
fpm (18 m/s).
(Added by Ord. 94-75; Am. Ord. 01-47)
Article 10. Heating, Ventilating and Air
Conditioning (HVAC) Equipment
Sections:
32-10.1 Scope.
32-10.2 General.
32-10.3 Basic requirements.
Sec. 32-10.1 Scope.
(a) The requirements of this article apply to new HVAC equipment installed in new
or existing buildings.
(b) Exception. This article does not apply to the maintenance or repair of existing
HVAC equipment.
(Added by Ord. 94-75)
Sec. 32-10.2 General.
HVAC equipment shall be supplied with the information necessary to make the analysis
required to determine compliance with this code.
(Added by Ord. 94-75)
Sec. 32-10.3 Basic requirements.
(a) Mechanical Equipment Efficiency.
(1) Equipment shown in Tables 10.1A through 10.1G shall have a minimum performance at
the specified rating conditions when tested in accordance with the specified test procedure.
Omission of minimum performance requirements for equipment not listed in Tables 10.1A through
10.1G does not preclude use of such equipment. Equipment not listed in Tables
10.1A through 10.1G has no minimum performance requirements. Where multiple rating conditions or
performance requirements are provided, the equipment shall satisfy all stated requirements, unless otherwise
exempted by footnotes in the table. However, equipment covered under the Federal Energy
Policy Act of 1992 (EPACT) shall have no minimum efficiency requirements for operation
at minimum capacity or other than standard rating conditions. Equipment used to provide
water heating functions as part of a combination system shall satisfy all stated
requirements for the appropriate space heating or cooling category.
(2) If a certification program exists for a product covered in Tables 10.1A through
10.1G, and it includes provisions for verification and challenge of equipment efficiency ratings,
then the product shall be either listed in the certification program or, alternatively,
the ratings shall be verified by an independent laboratory test report. If no
certification program exists for a product covered in Tables 10.1A through 10.1G, the
equipment efficiency ratings shall be supported by data furnished by the manufacturer. Where
components such as indoor or outdoor coils from different manufacturers are used, the
system designer shall specify component efficiencies whose combined efficiency meets the minimum equipment
efficiency requirements in this section.
(3) Tables 10.1A through 10.1G contain the minimum efficiency requirements for equipment covered by
this section of the standard. The tables are organized to cover the following
types of equipment:
(A) Table 10.1A Air Conditioners and Condensing Units;
(B) Table 10.1B Heat Pumps;
(C) Table 10.1C Water Chilling Packages;
(D) Table 10.1D Packaged Terminal and Room Air Conditioners and Heat Pumps;
(E) Table 10.1E Furnaces, Duct Furnaces and Unit Heaters;
(F) Table 10.1F Boilers; and
(G) Table 10.1G Heat Rejection Equipment.
(4) Gas-fired and oil-fired forced air furnaces with input ratings $ 225,000 Btu/h (65
kW) shall also have an intermittent ignition or interrupted device (IID), and have
either power venting or a flue damper. A vent damper is an acceptable
alternative to a flue damper for furnaces where combustion air is drawn from
the conditioned space. All furnaces with input ratings $ 225,000 Btu/h (65 kW),
including electric furnaces, that are not located within the conditioned space shall have
jacket losses not exceeding 0.75% of the input rating.
(5) Exceptions:
(A) Water-cooled centrifugal water-chilling packages that are not designed for operation at ARI Standard
550 test conditions (and thus cannot be tested to meet the requirements of
Table 10.1C) of 44°F leaving chilled water temperature and 85°F entering condenser water
temperature shall have a minimum full load COP and IPLV rating as shown
in Tables 10.1H, I, and J. The table values are only applicable over
the following full load design ranges:
(i) Leaving Chiller Water Temperature: 40 to 48°F;
(ii) Entering Condenser Water Temperature: 75 to 85°F; and
(iii) Condensing Water Temperature Rise: 5 to 15°F.
(B) Chillers designed to operate outside of these ranges are not covered by this
standard.
(b) Maintenance. Operation and maintenance information shall be provided with the equipment by the
equipment supplier.
Table 10.1A (I-P Units)
Unitary Air Conditioners and Condensing Units, Electrically Operated,
Minimum Efficienc y Requirements
Equipment Type
|
Size Category
|
Sub-Category or Rating Condition
|
Minimum Efficiencyb
|
Test Procedure
|
Air Conditioners,
Air Cooled
|
< 65,000 Btu/hd
|
Split System
|
10.0 SEER
|
ARI 210/240
|
|
|
|
Single Package
|
9.7 SEER
|
|
|
|
e65,000 Btu/h and
< 135,000 Btu/h
|
Split System and
Single Package
|
10.3 EERc
10.6 IPLVc
|
|
|
|
e135,000 Btu/h and
< 240,000 Btu/h
|
Split System and
Single Package
|
9.7 EERc
9.9 IPLVc
|
ARI 340/360
|
|
|
e 240,000 Btu/h and
<760,000 Btu/h
|
Split System and
Single Package
|
9.5 EERc
9.7 IPLVc
|
|
|
|
e760,000 Btu/h
|
Split System and
Single Package
|
9.2 EERc
9.4 IPLVc
|
|
Air Conditioners, Water and Evaporatively Cooled
|
< 65,000 Btu/h
|
Split System and
Single Package
|
12.1 EER
11.2 IPLV
|
ARI 210/240
|
|
|
e 65,000 Btu/h and
< 135,000 Btu/h
|
Split System and
Single Package
|
11.5 EERc
10.6 IPLVc
|
|
|
|
e135,000 Btu/h and
d240,000 Btu/h
|
Split System and
Single Package
|
11.0 EERc
10.3 IPLVc
|
ARI 340/360
|
|
|
> 240,000 Btu/h
|
Split System and
Single Package
|
11.0 EERc
10.3 IPLVc
|
|
Condensing Units,
Air Cooled
|
e135,000 Btu/h
|
|
10.1 EER
11.2 IPLV
|
ARI 365
|
Condensing Units,
Water or Evaporatively Cooled
|
e135,000 Btu/h
|
|
13.1 EER
13.1 IPLV
|
|
b IPLVs are only applicable to equipment with capacity modulation.
c Deduct 0.2 from the required EERs and IPLVs for units with a
heating section other than electric resistance heat.
d Single-phase air-cooled air-conditioners < 65,000 Btu/h are regulated by NAECA. SEER values
are those set by NAECA.
|
Table 10.1B (I-P Units)
Unitary and Applied Heat Pumps, Electrically Operated, Minimum Efficiency Requirements
Equipment Type
|
Size Category
|
Sub-Category or Rating Condition
|
Minimum Efficiencyb
|
Test Procedure
|
Air Cooled, (Cooling Mode)
|
< 65,000 Btu/hd
|
Split System
|
10.0 SEER
|
ARI 210/240
|
|
|
|
Single Package
|
9.7 SEER
|
|
|
|
e65,000 Btu/h and
< 135,000 Btu/h
|
Split System and
Single Package
|
10.1 EERc
10.4 IPLVc
|
|
|
|
e135,000 Btu/h and
<240,000 Btu/h
|
Split System and
Single Package
|
9.3 EERc
9.5 IPLVc
|
ARI 340/360
|
|
|
e240,000 Btu/h
|
Split System and
Single Package
|
9.0 EERc
9.2 IPLVc
|
|
Water-Source
(Cooling Mode)
|
< 17,000 Btu/h
|
85°F Entering Water
|
|
ARI 320
|
|
|
|
86°F Entering Water
|
11.2 EER
|
ARI/ISO-13256-1
|
|
|
e 17,000 Btu/h and
<65,000 Btu/h
|
85°F Entering Water
|
|
ARI 320
|
|
|
|
86°F Entering Water
|
12.0 EER
|
ARI/ISO-13256-1
|
|
|
e65,000 Btu/h and
< 135,000 Btu/h
|
85°F Entering Water
|
|
ARI 320
|
|
|
|
86°F Entering Water
|
12.0 EER
|
ARI/ISO-13256-1
|
Groundwater-Source
(Cooling Mode)
|
< 135,000 Btu/h
|
70°F Entering Water
50EF Entering Water
|
|
ARI 325
|
|
|
|
59°F Entering Water
|
16.2 EER
|
ARI/ISO-13256-1
|
Ground Source
(Cooling Mode)
|
< 135,000 Btu/h
|
77°F Entering Brine
70EF Entering Brine
|
|
ARI 330
|
|
|
|
77°F Entering Water
|
13.4 EER
|
ARI/ISO-13256-1
|
Air Cooled
(Heating Mode)
|
< 65,000 Btu/hd
(Cooling Capacity)
|
Split System
|
6.8 HSPF
|
ARI 210/240
|
|
|
|
Single Package
|
6.6 HSPF
|
|
|
|
e65,000 Btu/h and
< 135,000 Btu/h
(Cooling Capacity)
|
47°F db/43°F wb Outdoor Air
17°F db/15°F wb Outdoor Air
|
|
|
|
|
e135,000 Btu/h
(Cooling Capacity)
|
| |