Revised Ordinances of Honolulu(Link to original Word Processing Version)
(*Editors Note: Ordinance 09-30 shall take effect 60 days after its approval, November
28, 2009.) Chapter 32
BUILDING ENERGY CONSERVATION CODE
Articles: Article 1. Purpose
Sections: 32-1.1 Purpose and intent. Sec. 32-1.1 Purpose and intent. (a) The purpose of this chapter is to set minimum requirements for the energy-efficient design of buildings so that they may be constructed, operated, and maintained in a manner that minimizes the use of energy without constraining the building function or the comfort or productivity of the occupants. (b) The intent of this chapter is to provide criteria for the energy-efficient design and construction of buildings and this chapter is intended to provide flexibility to allow the use of innovative approaches and techniques to achieve the effective use of energy. This chapter will recognize the need for a modern, up-to-date energy conservation code addressing the design of energy-efficient building envelopes and installation of energy-efficient mechanical, lighting and power systems through requirements emphasizing performance. There may be instances in which the requirements of this code may conflict with requirements in health, safety or environmental codes, including the building code. In that case, the health, safety or environmental codes shall prevail. (Added by Ord. 09-30)
Article 2. General Provisions
Sections: 32-2.1 Definitions . Sec. 32-2.1 Definitions . In this chapter, unless the context otherwise requires: "Chapter" means Chapter 32 of this ROH. "ICC" means the International Code Council. "IECC" means the ICC, International Energy Conservation Code, 2006 Edition, as copyrighted by the International Code Council. "Section" means a section of a chapter of the International Energy Conservation Code. (Added by Ord. 09-30)
Article 3. Adoption of the International Energy Conservation Code
Sections: Sec. 32-3.1 Adoption of the International Energy Conservation Code. Sec. 32-3.1 Adoption of the International Energy Conservation Code. The "International Energy Conservation Code, 2006 Edition," as copyrighted and published in 2006 by the International Code Council, Incorporated, 500 New Jersey Avenue, 6th Floor, Washington, DC 20001, is adopted by reference and made a part of this chapter. This incorporation by reference includes all parts of the International Energy Conservation Code, subject to the amendments hereinafter set forth. The appendices of the ICC, IECC are not adopted except as provided in this chapter. (Added by Ord. 09-30)
Article 4. Amendments to the 2006 ICC
International Energy Conservation Code
(1) Amending Section 101.1. Section 101.1 is amended to read as follows:
101.1 Title . This code shall be known as the Building Energy Conservation Code
of the City and County of Honolulu, and shall be cited as such.
It is referred to herein as "this code."
(2) Amending Section 101.5.2. Section 101.5.2 is amended to read as follows:
101.5.2 Low Energy Buildings . The following buildings, or portions thereof, separated from the
remainder of the building by building thermal envelope assemblies complying with this code
shall be exempt from the building thermal envelope provisions of this code:
1. Conditioned spaces with a peak design rate of energy usage less than 3.4
Btu/h·ft2 (10.7 W/m2) or 1.0 watt/ft2 (10.7 W/m2) of floor area for space
conditioning purposes.
2. Unconditioned spaces that are non-habitable spaces.
(3) Amending Section 104.1. Section 104.1 is amended to read as follows:
104.1 General . When the requirements in this code apply to a building as
specified in Section 101.4, plans, specifications or other construction documents submitted for a
building, electrical, or plumbing permit required by this jurisdiction shall comply with this
code and shall be prepared, designed, approved, and observed by a design professional.
The responsible design professional shall provide on the plans a signed statement certifying
that the project is in compliance with this code.
Exception : Any building, electrical, or plumbing work that is not required to be
prepared, designed, approved, or observed by a licensed professional architect or engineer pursuant
to Chapter 464 of the Hawaii Revised Statutes.
104.3 Conformance Statement . The plan shall include the following conformance statement by the
responsible engineer or architect that the design conforms to this code.
(5) Deleting Section 105. Section 105 is deleted.
(6) Amending Table 402.1.1. Table 402.1.1 is amended to read as follows: TABLE 402.1.1
INSULATION AND FENESTRATION REQUIREMENTS BY COMPONENT a
a. Design Option is not allowed at building sites above a 2,400-foot elevation. 402.1.1.2 Definitions . For the purpose of this section, the following terms shall be defined as follows:
Gross Area of Opaque Roof Surfaces. Gross area of opaque roof surfaces means
the total surface of the roof assembly exposed to outside air or unconditioned
spaces. The opaque roof assembly shall exclude skylight surfaces, service openings, and overhangs.
Net Free Vent Area. Net free vent area means the total area through
which air can pass in a screen, grille face or register.
Roof Area. Roof area means attic floor area; or, if there is no
attic, "roof area" means the horizontal projection of roof area measured from the
outside surface of the exterior walls.
402.1.1.3 Construction Documents . Plans shall be submitted which indicate insulation type, thickness, and
location; ventilation opening types, sizes and locations; radiant barrier location; and, roof surface
type as appropriate, depending on the option selected from Table 402.1.1.1.
402.1.1.4 Roof Insulation . Roof insulation shall be provided as follows:
1. In buildings with an attic space provide either:
1.1. R-30 insulation installed above the ceiling level, or
1.2. R-19 insulation installed at the roof level between the roof framing members.
2. In buildings without an attic space provide either: 2.1. R-19 insulation installed at the roof level between the roof framing members. 2.2. R-15 insulation entirely above the roof deck. 402.1.1.5 Ventilation . Ventilation shall be provided by at least one of the following: 1. A baffled ridge vent installed in accordance with the manufacturer's instructions in addition to lower inlet openings to provide a total of no less than one square foot of net free vent area for each 300 square feet of roof area. No less than 30 percent of the total vent area shall be in either the ridge vent or the lower half of the ventilated space. 2. A solar-powered exhaust fan that provides at least one cubic foot per minute of airflow for each square foot of roof area. 3. Upper and lower vents with total net free vent area of at least one square foot for each 150 square feet of roof area. At least 30 percent of the total vent area shall be in the upper half of the ventilated space and at least 30 percent of the total vent area shall be in the lower half of the ventilated space.
402.1.1.6 Radiant Barrier . A radiant barrier shall have an emissivity of no greater
than 0.05 as tested in accordance with ASTM E-408. The radiant barrier shall
be installed with the shiny side facing down and with a minimum air
gap thickness of three-fourths (¾ ) inch. The radiant barrier may be securely
attached to the roof framing or may be laminated to the bottom of
the roof sheathing.
402.1.1.7 Cool Roof . A cool roof shall have an infrared emittance of no
more than 0.75 when tested in accordance with ASTM E-408 and a high
solar reflectance. The manufacturer's test results shall be acceptable for compliance.
402.1.1.8 Ro of Heat Gain Factor . The Roof Heat Gain Factor (RHGF) shall not
exceed 0.05 when calculated as described in Equation 402.1.1-1.
Equation 402.1.1-1
Where:
RHGF = Roof Heat Gain Factor (Btu/ft2-h-°F)
Ur = Overall thermal transmittance value for the gross area of opaque roof
surfaces (Btu/ft2-h-°F)
α = Roof surface absorptivity. Between 0.3 and 1.0 (unitless)
RB = Radiant Barrier credit. Equals 0.33 if a radiant barrier is installed
and 1.00 otherwise (unitless). Radiant barrier installation shall comply with Section 402.1.1.7.1 to
qualify for Radiant Barrier credit.
402.1.1.8.1 Radiant Barrier Credit . To qualify for the Radiant Barrier credit (RB) described
in Section 402.1.1.8, the installation of the radiant barrier shall meet the following
criteria:
1. The emissivity of the radiant barrier shall be 0.10 or less. The manufacturer
shall provide test data or documentation of the emissivity as tested in accordance
with ASTM E-408.
2. The radiant barrier shall be securely installed in a permanent manner using one
of the following installation methods:
2.1. The radiant barrier shall be draped with the reflective surface facing down over
the top cord of the truss before the roof deck is installed. A
minimum air gap of three-fourths (¾) inch shall be provided between the radiant
barrier and the roof deck above at the center of the span. A
minimum three-fourths (¾) inch air gap shall also be provided between the radiant
barrier and the ceiling or insulation below.
2.2. The radiant barrier shall be stretched with the shiny side facing down between
the top cords of the truss and stapled or otherwise secured at each
side. A minimum air space of three-fourths (¾) inch above and below is
required.
2.3. For attic installations only, the radiant barrier shall be stapled or otherwise secured
to the bottom surface of the top cord of the truss and draped
below with the shiny side facing down. A minimum air space of three-fourths
(¾) inch above and below is required.
2.4. For open beam ceiling construction only, the radiant barrier shall be laid on
top of the roof deck with the shiny side facing up and a
minimum three-fourths (¾) inch air gap between the radiant barrier and the roofing
material above. The roof slope shall be greater than or equal to 14°
from horizontal.
3. At least one square foot of free area for ventilation shall be provided
per 150 square feet of attic floor area, or in the case of
vaulted or open-beam ceilings, per 150 square feet of ceiling area. In vaulted
or open beam ceilings, the air space shall have an evenly-distributed vent area.
In vaulted ceilings, vents shall be provided for each air space between rafters.
(8) Amending Table 402.1.3. Table 402.1.3 is amended to read as follows: TABLE 402.1.3
EQUIVALENT U-FACTORS a
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||